A configuration file of OMRON UPS monitor daemon is common INI. It has 2 sections, one is [global] and other is device specified sections. Can't rename those. Key names and sample settings as below:
[global]
# UPS device section name
target=OMRON UPS BZ35T
# UPS device path / auto discovery
device=auto
# Buzzer enable / disable
buzzer=enable
# Battery test enable / disable
battery_test=enable
# Auto reboot enable / disable
auto_reboot=enable
# Shutdown command for normal time
shutdown_cmd=/sbin/shutdown -p now
# Shutdown command in emergency situations
em_shutdown_cmd=/sbin/halt -p
# Battery Check Interval [sec]
battery_check_interval=3

[OMRON UPS BZ35T]
# Battery charge level to start normal shutdown [%]
pc_shutdown_level=50
# Battery charge level to start emergency shutdown [%]
pc_em_shutdown_level=35
# Wait time to start UPS shutdown after monitered system shutdown started [min]
ups_shutdown_time=2
# Wait time to start power supply from UPS after main power supply to UPS returned [min]
ups_reboot_time=0

[OMRON UPS BZ50T]
pc_shutdown_level=40
pc_em_shutdown_level=30
ups_shutdown_time=2
ups_reboot_time=0

[OMRON UPS BZ50LT]
pc_shutdown_level=40
pc_em_shutdown_level=30
ups_shutdown_time=disable
ups_reboot_time=0
sample of configuration file
A daemon process can monitor only one UPS device with a configuration file at the same time. If you want to monitor many UPS devices, create appropriate configuration files for each UPS devices and start monitor daemons for each devices with those configrations.